Features
• Upper and lower setpoint limit stops
• Dual scale setpoint indication
• Digital contact for operating mode selection*
• Built-in temperature sensor
• Selectable DIP switches for setting various
control parameters
• Heating only, cooling only or heating and
cooling applications
• Attractively styled, modern housing
• Automatic or manual changeover selection
• Freeze protection mode*
*except RCU50.2U
Specifications
Operating voltage .......................24 Vac
Frequency ...................................50/60 Hz
Setpoint range ............................50°F to 85°F
(10°C to 30°C)
Setpoint limit stops ......................Adjustable
Switch rating at 24 Vac ................ 6 (1)A
resistive
(inductive)
Control Action .............................See table.
Output
Product Heating Cooling
RCU15U On/off/PWM On/off/PWM
RLA162.5U 0 to 10 Vdc 0 to 10 Vdc
RCU50U 0 to 10 Vdc 0 to 10 Vdc
RCU50.2U 0 to 10 Vdc 0 to 10 Vdc
RCU61U 3P 0 to 10 Vdc
Weight ........................................0.5 oz. (0.23 kg)
Color ...........................................Ivory white (cover)
Gray (base)
Ambient conditions
Operation temperature ...........32°F to 122°F
(0°C to 50°C)
Operation rh ...........................<95%
Transportation temperature ....–13°F to 158°F
(–25°C to 70°C)
Transportation rh ....................<95%
Wiring
Screw terminals ......................2 × 16 AWG or
1 × 14 AWG
20 AWG Maximum
Agency certifications ...................UL listed to UL 873
cUL certified to
Canadian Standard
C22.2 No. 24-33
Submittal Summary
Universal
Room Control
RCU... Series Electronic Room Temperature Controllers
Microprocessor-
controlled
constant air
volume room
controller is
designed for air
only or air and
water heating,
and/or cooling
systems with
proportional (P)
response.
RCU15U • •* • • •
RLA162.5U • • • •
RCU50U • • • •
RCU50.2 • • •
Free Energy Band™ • • • • •
RCU61U
Part Number Application Control Output Changeover
2-pipe
4-pipe
Cooling/
heating
0 to 10 Vdc
PWM
On/off
Floating 3P
Reversible
Auto
Manual
* Reverse Acting (RA) heating/
Direct Acting (DA) cooling